- Non-Contact Ground Resistance Measurement
- No Auxiliary Electrode Needed
- Jaw Diameter £X 23 mm (5601)
- Jaw Diameter £X 35 mm(5637)
- 0.025 ¡V 1500 Ohm
|
- 0.2mA¡V 30A(5601)0.2mA¡V 35A(5637),True RMS
- 116 Sets of Memory(5601,5637)
- Programmable Hi and Lo Alarm(5601,5637)
- Programmable Data Logging (5601,5637)
|
|
- Telecommunication
- Cable TV system
- Electrical Power Plant
|
- Cellular Phone System
- Factory and Facility
- Gas Station Tank
|
 |
¡@ |
| Ground Resistance (Auto range) |
Range |
Resolution |
Accuracy of Reading 1,2 |
| 0.025 - 0.250 £[ |
0.002 £[ |
¡Ó 1.5% ¡Ó 0.05
£[ |
| 0.250 - 1.000 £[ |
0.02 £[ |
¡Ó 1.5% ¡Ó 0.05
£[ |
| 1.001 - 9.999 £[ |
0.02 £[ |
¡Ó 1.5% ¡Ó 0.1
£[ |
| 10.00 - 50.00 £[ |
0.04 £[ |
¡Ó 2.0% ¡Ó 0.3
£[ |
| 50.01 - 99.99 £[ |
0.04 £[ |
¡Ó 2.0% ¡Ó 0.5
£[ |
| 100.0 - 200.0 £[ |
0.4 £[ |
¡Ó 3.0% ¡Ó 1.0
£[ |
| 200.1 - 400.0 £[ |
2 £[ |
¡Ó 5.0% ¡Ó 5 £[ |
| 400.1 - 600.0 £[ |
5 £[ |
¡Ó 10% ¡Ó 10 £[ |
| 600.1 - 1500 £[ |
20 £[ |
¡Ó 20% |
| 1 Loop resistance noninductive, external field < 200 A/m, external electrical field < 1 V/m, conductor centered.
2 Resistance Measurement Frequency: 1.667KHz,3.333KHz(optional) |
|
| Ground/Leakage Current (Auto range, 50/60 Hz, True RMS, Crest Factor < 3.5) |
Range |
Resolution |
Accuracy of Reading |
| 0.200 - 1.000 mA |
0.001 mA |
¡Ó 2.0% ¡Ó 0.05 mA |
| 1.00 - 10.00 mA |
0.01 mA |
¡Ó 2.0% ¡Ó 0.03 mA |
| 10.0 - 100.0 mA |
0.1 mA |
¡Ó 2.0% ¡Ó 0.3 mA |
| 100 - 1000 mA |
1 mA |
¡Ó 2.0% ¡Ó 3 mA |
| 0.20 - 4.00 A |
0.001A |
¡Ó 2.0% ¡Ó 0.03A |
| 4.00 - 30.00 A(5601) |
0.01A |
¡Ó 3.0% ¡Ó 0.03A |
| 4.00 - 35.00 A(5637) |
0.01A |
¡Ó 3.0% ¡Ó 0.03A |
|
| Accuracy of Resistance Calibration Plate |
¡Ó0.5% |
| Data Logging Capacity |
116 records |
| Data Logging Interval |
1 to 255 seconds |
| Conductor Size |
35mm /1.38¡¨(5637), 23mm /0.90¡¨(5600,5601) |
| Jaw Opening |
38mm /1.49¡¨(5637), 27mm /1.06¡¨(5600,5601) |
| Battery Type |
9V IEC 6 LR61 (Alkaline) |
| Display Type |
4 digits 9999 counts LCD |
| Overload Indication |
OL |
| Battery Life |
3000 measurements |
| Low Battery Indication |
¡@ |
| Range Selection |
Auto |
| Power Consumption |
40mA |
| Sampling Time |
0.5 seconds |
| Operating Temperature |
0
¢J
to 50
¢J
(14
¢K
to 122
¢K
) Operating Humidity: Less than 85% RH |
| Storage Temperature |
-20
¢J
to 60
¢J
(-4
¢K
to 122
¢K
) Storage Humidity: Less than 75% RH |
| Dimension( 5637 |
276mm (L) x 100mm(W) x 47mm(H),10.8" (L) x 3.9"(W) x 1.9"(H) |
| Dimension( 5600,5601 ) |
257mm (L) x 100mm(W) x 47mm(H),10.1" (L) x 3.9"(W) x 1.9"(H) |
| Weight( 5637) |
750g/1.65lbs |
| Weight( 5600,5601) |
640g/1.41lbs |
| Accessories |
- Resistance Calibration Plate x 1
- Battery 9V (Installed) x 1
- Carrying Box x 1
- Users Manual x 1
|
|
¡@
|
|
TES Electrical Electronic Corp. |
- Office: 7F, No. 31, Lane 513, Rui Guang Road,
Neihu Dist., Taipei, Taiwan, R.O.C.
- TEL:886-2-2799-3660 FAX:886-2-2799-5099
- E-Mail: tes@ms9.hinet.net
|
|