Flexible Clamp Meter

Home > Products > DC/AC Flexible Clamp Meter > Graphic Power Quality Analyzer
AFLEX-6300

Graphic Power Quality Analyzer

Product Features
  • Power Quality Analysis for Single and Balanced Three Phase System
  • Harmonic Analysis of Voltage and Current (1 to 50th order)
  • True RMS measurement of V with 0.5% basic accuracy
  • True RMS measurement of A with 1% of range basic accuracy
  • Graphic Waveform of Voltage and Current
  • Graphic Phasor Diagram
  • Transient Detection and Logging of Swell, Dip, and Outage
  • Fast peak function (39μs for 50 Hz, 33μs for 60Hz)
  • Active (W, KW, HP), reactive (VAR, KVAR) and apparent (VA, KVA) power
  • Power factor (PF), phase angle (Φ), and energy (WH, KWH)
  • Measurement of balanced 3Φ Power Quality
  • Programmable VT ratio from 1 to 3000
  • Hold functions
  • Auto power off function in 15 minutes
Graphic Power Quality Analyzer

Electrical Specifications: (23±5)

AC Watt

Range

Resolution

Accuracy of Readings

> 20 V and > 30A

< 20V or < 30A

10.0 – 999.9 W

0.1W

±1% of Range ±0.3W

±2% of Range

1.000 – 9.999 KW

0.001 KW

±1% of Range ±0.003KW

±2% of Range

10.00 – 99.99 KW

0.01 KW

±1% of Range ±0.03KW

±2% of Range

100.0 – 999.9 KW

0.1 KW

±1% of Range ±0.3KW

±2% of Range

1000 – 9999 KW

1 KW

±1% of Range ±3KW

±2% of Range

AC Apparent Power (VA)

Range

Resolution

Accuracy of Readings

> 20 V and > 30A

 

10.0 – 999.9 VA

0.1VA

±1% of Range ±0.3VA

±2% of Range

1.000 – 9.999 KVA

0.001 KVA

±1% of Range ±0.003KVA

±2% of Range

10.00 – 99.99 KVA

0.01 KVA

±1% of Range ±0.03KVA

±2% of Range

100.0 – 999.9 KVA

0.1 KVA

±1% of Range ±0.3KVA

±2% of Range

1000 – 9999 KVA

1 KVA

±1% of Range ±3KVA

±2% of Range

 AC Reactive Power (VAR)

Range

Resolution

Accuracy of Readings

> 20 V and > 30A

 

10.0–999.9 VAR

0.1VAR

±1% of Range ±0.3VAR

±2% of Range

1.000–9.999 KVAR

0.001 KVAR

±1% of Range ±0.003KVAR

±2% of Range

10.00–99.99 KVAR

0.01 KVAR

±1% of Range ±0.03KVAR

±2% of Range

100.0–999.9 KVAR

0.1 KVAR

±1% of Range ±0.3KVAR

±2% of Range

1000 – 9999 KVAR

1 KVAR

±1% of Range ±3KVAR

±2% of Range

Power Factor (PF)

Range

Resolution

Accuracy

> 20V & > 30A

< 20V or < 30A

0.000 – 1.000

0.001

± 0.04

±0.1

 AC Current

Range

Resolution

Accuracy of Readings

3A – 300.0A

0.1A

±1% of Range ±0.3A

300.0 – 3000A

0.1A / 1A

±1% of Range ±3A

AC Voltage (Overload Protection AC 800V)

Range

Resolution

Accuracy of Readings

4.0 V – 600.0 V

0.1 V

±0.5% ± 5dgts

Harmonics of AC Voltage in Percentage

Range

Resolution

Accuracy

1 – 20th

0.1%

±2%

21 – 50th

0.1%

4% of reading ±2.0%

Harmonics of AC Voltage in Magnitude

Range

Resolution

Accuracy

1 – 20th

0.1%

±2% ± 0.5V

21 – 50th

0.1%

4% of reading ±0.5V

Harmonics of AC Current in Percentage

Range

Resolution

Accuracy

1 – 20th

0.1%

±2%

21 – 50th

0.1%

±6%

Harmonics of AC Current in Magnitude (True RMS < 300A)

Range (0 – 300A)

Resolution

Accuracy

1 – 20th

0.1%

±2% of range ±0.4A

21 – 50th

0.1%

±4% of range ±0.4A

Harmonics of AC Current in Magnitude (3000A >True RMS> 300A)

Range

Resolution

Accuracy

1 – 20th

0.1%

±2% of range ±40A

21 – 50th

0.1%

±4% of range ±40A

 Phase Angle (Φ, V > 20V, A > 30A)

Range

Resolution

Accuracy

-180° to 180°

0.1°

± 2°

0° to 360°

0.1°

± 2°

Total Harmonic Distortion

Range

Resolution

Accuracy

0.0 – 20%

0.1%

± 2%

20 – 100%

0.1%

± 7%

100 – 999.9 %

0.1%

± 11%

Peak Value of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)

Range

Sampling Time

Accuracy of Reading

50 Hz

39 μs

± 5% ± 50 digits

60 Hz

33 μs

± 5% ± 50 digits

Frequency of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)

Range

Resolution

Accuracy

46 – 65

0.1

± 0.3Hz

 

General Specifications: 

Probe Length: 6300-24  

24 in / 610 mm

Minimum Bending Diameter:  

35mm

Connector Diameter:

23mm

Cable Diameter:

14mm

Cable Length from Probe to Box:

1700mm

Cable Length from Box to Output:

1700mm

Data Logging Memory Size:

512K bytes

Maximum Transient Events:

32000

Dimension (Box):

130 (L) x 80 (W) x 43 (H) mm

5.1” (L) x 3.1” (W) x 1.7” (H)

Battery Type:

two 1.5V SUM-3

Display:

128 X 64 Dot Matrix LCD with Backlight

Range Selection:

Auto

Overload Indication:

OL

Power Consumption: 

10mA (approx)

Auto-Power-Off:

15 minutes after power-on

LCD Update Time:

2 times/sec.

No. Of Samples per Period

512 (voltage or current); 256 (power)

Operating Temperature:

-10°C to 85°C

Operating Humidity:

15% to 85% RH

Altitude:

up to 2000M

Storage Temperature:

-20°C to 85°C

Storage Humidity:

15% to 85% RH

Weight:

430g (battery included)

Accessories:

Test leads (red/black) x 1 set

Users manual x 1

Batteries 1.5V x 2

Carrying Case x 1

Software CD x 1

Software users manual x 1

USB to RS232 cable x 1