HVAC Trms Clamp Meter

Home > Products > DC/AC HVAC Trms Clamp Meter > AC 1000A Clamp Meter
AC 1000A Clamp Meter
TES-3079M

AC 1000A Clamp Meter

Product Features
  • 10 in 1 multifunction clamp meter
  • Voltage, Current, Power, Horse power, Reactive power, Apparent power, Phase angle, Frequency, Power factor, Phase sequence, Temperature, Resistance, Capacitance, Diode
  • Trms reading/Dual display/Auto power off

 ELECTRICAL SPECIFICATIONS (23±5) 

AC Current (50Hz to 400Hz) : Trms 

Range
Resolution
Accuracy
Sensitivity
Overload Protection
99.99A
   10mA
±2% ±30dgts (50, 60Hz)
±4% ±30dgts (40~400Hz)
0.10A
1000A ac
999.9A
  100mA
1.0A

 

ACA Inrush Current : 

Range
Resolution
Sensitivity
Measurement Time
Overload Protection
99.99A
0.01A
>5A
100mS
1000A ac
999.9A
0.1A
>50A

 

mA Trms : (AC+DC) (Burden Voltage : 5mV/µA) 
Range
Resolution
Accuracy
Sensitivity
Overload Protection
99.99mA
   10nA
±1% ±30dgts
0.20µA
600V
999.9mA
  100nA
2.0µA

 

AC Voltage (50Hz to 400Hz) : Trms 

Range
Resolution
Accuracy
Sensitivity
Overload Protection
999.9mV
0.1mV
±1% ±30dgts (50, 60Hz)
±2% ±30dgts (40~400Hz)
2.0mV
600V ac
9.999V
1mV
0.020V
99.99V
10mV
0.20V
600.0V
  100mV
2V

 

DC Voltage 

Range
Resolution
Accuracy
Sensitivity
Overload Protection
999.9mV
0.1mV
±1.0% ±30dgts
2.0mV
600V
9.999V
1mV
0.020V
99.99V
10mV
0.20V
600.0V
  100mV
2V

 

Resistance (Continuity<40Ω on the 999.9Ω range) : 

Range
Resolution
Accuracy
Overload Protection
999.9Ω
100mΩ
±1% ±10dgts
600V
9.999KΩ
1Ω
99.99KΩ
10Ω
999.9KΩ
100Ω

 

: 

Range
Resolution
Accuracy
Overload Protection
9.999MΩ
1KΩ
±5% ±10dgts
600V
99.99MΩ
10KΩ

 3∅ Phase sequence indication : 

Range
Frequency Response
Overload Protection
80V to 480V
50Hz / 60Hz
600V ac

  Capacitance : 

Range
Resolution
Accuracy
Overload Protection
10.000μF
1nF
±1.5% ±5dgts
600V
100.00μF
10nF
1000.0μF
100nF
7000μF
F
±2.5% ±15dgts

 Diode (Continuity<40mV) : 

Range
Resolution
Accuracy
Overload Protection
2.000V
1mV
±2% ±1dgt
600V

 Temperature (K-Type ther mocouple) : 

Range
Resolution
Accuracy
Overload Protection
-50ºC to 900ºC
0.1ºC
±0.2% ±1ºC
30V ac or 60V dc
-58ºF to 1000ºF
0.1ºF
±0.2% ±2ºF

 1f/3f TRUE Power (KW): (PF>0.5 or θ<60º ) 

Range
Resolution
Accuracy
Overload Protection
99.99KW
10W
±5%rdg ±30dgts
(50, 60Hz)
600V ac / 1000A ac
600.0KW
100W

 

1∅/3∅ Horse Power (HP): (PF>0.5 or θ<60º ) 

Range
Resolution
Accuracy
Overload Protection
99.99HP
0.01HP
±5%rdg ±30dgts
(50, 60Hz)
600V ac / 1000A ac
800.0HP
0.1HP

 

1∅/3∅Apparent Power : 

Range Resolution Accuracy Overload Protection
99.99KVA 10VA
±2.5%rdg ±30dgts
600V ac/
1000A ac
600.0KVA 100VA

 

1∅/3∅Phase Angle : (50Hz, 60Hz) 

Range
Resolution
Accuracy
Sensitivity
-60° ~ 0° ~ +60°
0.1º
±6.0º
ACV>100V, ACA>10A

 

Frequency : 

Range
Resolution
Accuracy
Sensitivity
40Hz/1KHz
0.1Hz
±0.5%rdg ±2dgts
ACV>1.2V, ACA>6A

 

 

 

 

 

HVAC Application :

¨ Check current draw in motors and compressors.

¨ Use MAX/MIN/Recording in the temperature mode to assess efficiency.

¨ Test run/start capacitors.

¨ Confirm low voltage control signals.

¨ Measure flame safeguard device current draw.

¨ Confirm power sources

¨ Analyze temperature and power data with the aid of the time stamp.

¨ Insulation test up to 100MΩ.

 

Electrical Application :

¨ Check for energized circuits and balance loads.

¨1ψ/3ψ(3P3W/3P4W) Power analyzer.

¨ Evaluate electrical contacts.

¨ Capture inrush current readings of motor.

¨ Determine peak power demand periods.

¨ Verify line voltage stability.

¨ Monitor motors and other loads for excess heat.

¨ Check motor run/start capacitor values.

¨Check 3f phase sequence.